NSN 5925-01-090-6374

Circuit Breaker

FSC: 5925     NIIN: 010906374

DODParts.com distributes circuit breakers, aircraft parts and consumables, electrical parts, fittings and other components for the aerospace and defense industries. Submit the short price quote form for NSN 5925-01-090-6374 to receive an up to date pricing and availability quote by email.

Product Characteristics

NSN:
5925010906374
Demilitarization:
NO
INC:
00136
Shelf Life:
N/A
Body Style:
Multipole-multiple actuator type
Body Length:
Between 1.968 inches and 2.032 inches
Body Width:
Between 1.468 inches and 1.562 inches
Case Material:
Plastic
Center To Center Distance Between Terminals Parallel To Length:
Between 1.528 inches and 1.592 inches
Center To Center Distance Between Terminals Parallel To Width:
Between 0.718 inches and 0.782 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length:
Between 1.628 inches and 1.692 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width:
Between 0.718 inches and 0.782 inches
Fragility Factor:
Moderately rugged
Boss Height:
Between 0.098 inches and 0.162 inches
Mounting Surface To Terminal End Distance:
Between 1.843 inches and 1.907 inches
Pole Quantity:
2
Arc Quenching Method:
Magnetic blowout
Mounting Facility Type And Quantity:
4 threaded hole
Storage Type:
General purpose warehouse
Thready Qty Per Inch (tpi):
32
Maximum Continuous Load Current Rating Per Pole:
30.0 amperes ac all locations
Operating Voltage Type And Rating Per Pole In Volts:
240.0 ac all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
5000.0 ac all locations
Circuit Protection Type:
Overcurrent all locations
Trip Release Method:
Magnetic-hydraulic all locations
Trip Release Characteristic:
Time delay all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
Reset Method:
Manual
Main Contact Tripping Mechanism Type:
Trip free
Manual Actuator Type And Quantity:
2 toggle
Actuator Function:
Trip-reset
Actuator Position Designation:
At each pole
External Actuator Linkage Arrangement:
One and two linked
Internal Trip Release Configuration:
Series trip all locations
Thread Size:
0.138 inches
Trip Delay Time In Seconds Per Rated Continuous Current:
4.500 at 300 pct all locations and 22.000 at 300 pct all locations
Inclosure Protection Type For Which Designed:
Fungus resistant and moisture resistant
Frequency In Hertz:
50.0 all locations or 60.0 all locations
Unpackaged Unit Weight:
7.500 ounces
Thread Series Designator:
Unc
Terminal Type And Quantity:
4 tab w/screw

Part Numbers

  • 36-022F01M00R00
    CONCURRENT COMPUTER CORPORATION
  • JA2-T8-A-30-10
    EATON CORP
  • JA2-T8-EB-01-D-A-30-10
    EATON CORP

Shipping & Handling

HMIRS:

No information in HMIRS. Hazardous material unknown.

ESD:

No known electrostatic discharge.

Schedule B:

8536200040 - Automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi.

Professional Distribution

  •   ITAR Registered
  •   DDTC Registered
  •   HAZMAT Certified
  •   AS9120 Quality Standards
  •   100% Quality Inspections
ITAR registered supplier

Need current pricing? Get a quote

Receive an official quote via email with pricing, availability, condition, and certifications when you submit this form below.

Qty:
Email Address:

NSN: 5925-01-090-6374 circuit breaker
Your Name:
Phone Number:
Company:
Privacy Policy    Order Terms
McAfee Secure