NSN 5925-00-410-1722

Circuit Breaker

FSC: 5925     NIIN: 004101722

DODParts.com distributes circuit breakers, aircraft parts and consumables, electrical parts, fittings and other components for the aerospace and defense industries. Submit the short price quote form for NSN 5925-00-410-1722 to receive an up to date pricing and availability quote by email.

Product Characteristics

NSN:
5925004101722
Demilitarization:
NO
INC:
00136
Shelf Life:
N/A
Body Length:
6.218 inches
Body Width:
4.125 inches
Body Height:
3.406 inches
Case Material:
Plastic
Center To Center Distance Between Terminals Parallel To Length:
5.218 inches
Center To Center Distance Between Terminals Parallel To Width:
1.375 inches
Unthreaded Mounting Hole Diameter:
0.250 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length:
5.125 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width:
1.375 inches
Boss Height:
0.250 inches
Pole Quantity:
3
Mounting Facility Type And Quantity:
4 unthreaded hole
Maximum Continuous Load Current Rating Per Pole:
80.0 amperes ac all locations and 80.0 amperes dc all locations
Operating Voltage Type And Rating Per Pole In Volts:
480.0 ac all locations and 250.0 dc all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
15000.0 ac all locations and 10000.0 dc all locations
Circuit Protection Type:
Overcurrent all locations
Trip Release Method:
Thermal-magnetic all locations
Trip Release Characteristic:
Time delay all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
Reset Method:
Manual
Main Contact Tripping Mechanism Type:
Trip free
Manual Actuator Type And Quantity:
1 toggle
Actuator Function:
Reset
Actuator Position Designation:
At pole two
Trip Delay Time In Seconds Per Rated Continuous Current:
25.000 at 200 pct all locations and 75.000 at 200 pct all locations and 5.100 at 300 pct all locations and 15.000 at 300 pct all locations
Trip Release Ambient Tempurature Rating:
40.0 degrees celsius all locations
Frequency In Hertz:
400.0 all locations
Terminal Type And Quantity:
6 compression

Part Numbers

  • NEF431080
    CHALLENGER ELECTRICAL EQUIPMENT CORP
  • NEF435080
    CHALLENGER ELECTRICAL EQUIPMENT CORP

Shipping & Handling

HMIRS:

No information in HMIRS. Hazardous material unknown.

ESD:

No known electrostatic discharge.

Schedule B:

8536200040 - Automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi.

Professional Distribution

  •   ITAR Registered
  •   DDTC Registered
  •   HAZMAT Certified
  •   AS9120 Quality Standards
  •   100% Quality Inspections
ITAR registered supplier

Need current pricing? Get a quote

Receive an official quote via email with pricing, availability, condition, and certifications when you submit this form below.

Qty:
Email Address:

NSN: 5925-00-410-1722 circuit breaker
Your Name:
Phone Number:
Company:
Privacy Policy    Order Terms
McAfee Secure