NSN 5925-00-201-4793

Circuit Breaker

FSC: 5925     NIIN: 002014793

DODParts.com distributes circuit breakers, aircraft parts and consumables, electrical parts, fittings and other components for the aerospace and defense industries. Submit the short price quote form for NSN 5925-00-201-4793 to receive an up to date pricing and availability quote by email.

NSN 5925-00-201-4793 Description

Multipole-single actuator type body style, 5.240 inches body length, 2.990 inches body width, plastic case material, 4.349 inches center to center distance between terminals parallel to length.

Product Characteristics

NSN:
5925002014793
Demilitarization:
NO
INC:
00136
Shelf Life:
N/A
Body Style:
Multipole-single actuator type
Body Length:
Between 5.240 inches and 5.260 inches
Body Width:
Between 2.990 inches and 3.010 inches
Case Material:
Plastic
Center To Center Distance Between Terminals Parallel To Length:
Between 4.349 inches and 4.369 inches
Center To Center Distance Between Terminals Parallel To Width:
Between 0.990 inches and 1.010 inches
Unthreaded Mounting Hole Diameter:
0.190 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length:
Between 4.349 inches and 4.369 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width:
Between 0.990 inches and 1.010 inches
Fragility Factor:
Moderately rugged
Boss Height:
Between 0.208 inches and 0.228 inches
Mounting Surface To Terminal End Distance:
Between 3.302 inches and 3.322 inches
Pole Quantity:
3
Arc Quenching Method:
Magnetic blowout
Mounting Facility Type And Quantity:
4 unthreaded hole
Storage Type:
General purpose warehouse
Maximum Continuous Load Current Rating Per Pole:
25.0 amperes dc all locations
Operating Voltage Type And Rating Per Pole In Volts:
125.0 dc all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
5000.0 dc all locations
Circuit Protection Type:
Overcurrent all locations
Trip Release Method:
Magnetic-hydraulic all locations
Trip Release Characteristic:
Time delay all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
Reset Method:
Manual
Main Contact Tripping Mechanism Type:
Trip free
Manual Actuator Type And Quantity:
1 toggle
Actuator Function:
Trip-reset
Actuator Position Designation:
At pole two
Internal Trip Release Configuration:
Series trip all locations
Trip Delay Time In Seconds Per Rated Continuous Current:
3.000 at 200 pct all locations and 10.000 at 200 pct all locations
Inclosure Protection Type For Which Designed:
Dustproof and fungus proof
Terminal Type And Quantity:
6 threaded stud

Part Numbers

  • 0142-25DCCURVEUN90
    EATON CORP
  • 1090142
    CHIEF OF ENGINEERS
  • 3363S-25-125-2-VDC
    EATON CORP
  • 3363S-25-125VDC-2
    EATON CORP
  • 3363S25DCCURVE2
    EATON CORP

Shipping & Handling

HMIRS:

No information in HMIRS. Hazardous material unknown.

ESD:

No known electrostatic discharge.

Schedule B:

8536200040 - Automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi.

Professional Distribution

  •   ITAR Registered
  •   DDTC Registered
  •   HAZMAT Certified
  •   AS9120 Quality Standards
  •   100% Quality Inspections
ITAR registered supplier

Need current pricing? Get a quote

Receive an official quote via email with pricing, availability, condition, and certifications when you submit this form below.

Qty: