NSN 5925-00-185-1442

Circuit Breaker

FSC: 5925     NIIN: 001851442

DODParts.com distributes circuit breakers, aircraft parts and consumables, electrical parts, fittings and other components for the aerospace and defense industries. Submit the short price quote form for NSN 5925-00-185-1442 to receive an up to date pricing and availability quote by email.

NSN 5925-00-185-1442 Description

Single pole type body style, 2.500 inches body length, 0.750 inches body width, plastic case material, 1.938 inches center to center distance between terminals parallel to length.

Product Characteristics

NSN:
5925001851442
Demilitarization:
NO
INC:
00136
Shelf Life:
N/A
Body Style:
Single pole type
Body Length:
2.500 inches
Body Width:
0.750 inches
Case Material:
Plastic
Center To Center Distance Between Terminals Parallel To Length:
1.938 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length:
2.062 inches
Switch Contact Arrangement:
Single pole, double throw
Fragility Factor:
Moderately rugged
Boss Height:
0.140 inches
Mounting Surface To Terminal End Distance:
Between 2.409 inches and 2.533 inches
Pole Quantity:
1
Arc Quenching Method:
Magnetic blowout
Mounting Facility Type And Quantity:
2 threaded hole
Storage Type:
General purpose warehouse
Special Handling Feature:
Magnetic
Thready Qty Per Inch (tpi):
32
Maximum Continuous Load Current Rating Per Pole:
3.0 amperes ac single location
Operating Voltage Type And Rating Per Pole In Volts:
120.0 ac single location
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
1000.0 ac single location
Circuit Protection Type:
Overcurrent single location
Trip Release Method:
Magnetic-hydraulic single location
Trip Release Characteristic:
Time delay single location
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 single location
Reset Method:
Manual
Main Contact Tripping Mechanism Type:
Trip free
Manual Actuator Type And Quantity:
1 toggle
Actuator Function:
Trip-reset
Actuator Position Designation:
At pole one
Auxiliary Switch Function And Quantity:
1 alarm
Internal Trip Release Configuration:
Series trip single location
Thread Size:
0.138 inches
Switch Location And Position Designation:
Internal at pole one
Trip Delay Time In Seconds Per Rated Continuous Current:
3.000 at 200 pct single location and 10.000 at 200 pct single location
Inclosure Protection Type For Which Designed:
Fungus resistant and humidity resistant and salt spray proof
Switch Terminal Type:
Tab, solder lug
Switch Current Rating And Type In Amps:
5.0 ac
Switch Voltage Rating And Type In Volts:
115.0 ac
Frequency In Hertz:
50.0 single location or 60.0 single location
Unpackaged Unit Weight:
0.312 pounds
Test Data Document:
08935-280-0009 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
Thread Series Designator:
Unc
Terminal Type And Quantity:
2 threaded stud

Part Numbers

  • 280-0009-02
    GRANGER ASSOCIATES
  • AM12HEMG6-3-120-4-50/60
    EATON CORP

Shipping & Handling

HMIRS:

No information in HMIRS. Hazardous material unknown.

ESD:

No known electrostatic discharge.

Schedule B:

8536200040 - Automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi.

Professional Distribution

  •   ITAR Registered
  •   DDTC Registered
  •   HAZMAT Certified
  •   AS9120 Quality Standards
  •   100% Quality Inspections
ITAR registered supplier

Need current pricing? Get a quote

Receive an official quote via email with pricing, availability, condition, and certifications when you submit this form below.

Qty:
Email Address:

NSN: 5925-00-185-1442 circuit breaker
Your Name:
Phone Number:
Company:
Privacy Policy    Order Terms
McAfee Secure